{"id":5270,"date":"2026-09-30T07:35:19","date_gmt":"2026-09-29T23:35:19","guid":{"rendered":"https:\/\/www.raxdoors.com\/blog\/fire-shutter-weekly-inspection-guide\/"},"modified":"2026-10-14T06:07:18","modified_gmt":"2026-10-13T22:07:18","slug":"fire-shutter-weekly-inspection-guide","status":"publish","type":"post","link":"https:\/\/www.raxdoors.com\/de\/blog\/fire-shutter-weekly-inspection-guide\/","title":{"rendered":"Inspektion von Feuerschutzroll\u00e4den: Ein w\u00f6chentlicher bis j\u00e4hrlicher Plan"},"content":{"rendered":"<p>The annual fire test reaches the shutter last in the round. A technician presses the release, and everyone in the aisle watches a curtain that has not moved in a year drop across the opening. On a good day it lands on the sill and the visit moves on. On the bad day, it stops short, leaving a metre of clear air between the bottom rail and the floor.<\/p>\n<p>We build industrial doors at our own factory, and fire shutters are the one line whose failures stay silent. Nothing judders, nothing leaks, nothing slows the shift while a fire shutter decays. The first symptom is the one nobody wants, so a fire shutter inspection routine exists to surface it early. It runs on three clocks: weekly, monthly and annual.<\/p>\n<h2 id=\"why-a-fire-shutter-gets-its-own-routine\">Why a Fire Shutter Gets Its Own Routine<\/h2>\n<p>A fire shutter is standby equipment. It hangs above the opening year after year, adds nothing to the working day, and is expected to close automatically the one time it is truly needed. Most industrial doors in daily traffic earn their maintenance honestly, complaining long before they quit. This one never does, and the standards treat that expectation seriously. The DASMA guidance for rolling steel fire doors notes that the annual requirement applies to all fire doors, even those that are never operated and remain closed.<\/p>\n<p>That expectation rests on a release chain rather than a motor switch. When the alarm sounds, one of several triggers has to let the curtain fall.<\/p>\n<ul>\n<li>A fire alarm interface releases the shutter on a signal from the panel.<\/li>\n<li>Smoke detectors actuate the closing mechanism directly.<\/li>\n<li>A fusible link separates when heat reaches it.<\/li>\n<li>A local test switch allows a controlled release for maintenance.<\/li>\n<\/ul>\n<p>The label on the curtain proves how the assembly performed in a laboratory test. It cannot prove what the installed system will do today, because a swapped motor, a repaired guide or a modified wall can change that approved performance. The distinction between rating and state is the same one we draw in our guide to <a href=\"https:\/\/www.raxdoors.com\/blog\/fire-rated-industrial-roller-shutters\/\">EI-rated industrial roller shutters<\/a>. The rating is decided once, in a fire test. The state is decided on site, every week after installation.<\/p>\n<p>The fire shutter inspection logic fits in one sentence. NFPA 80 sets the floor: an inspection and drop test at least once a year, conducted by a trained fire door technician. Everything shorter than a year is the routine that keeps the annual test from being the only line of defence.<\/p>\n<h2 id=\"the-weekly-walkthrough-five-minutes-at-the-opening\">The Weekly Walkthrough: Five Minutes at the Opening<\/h2>\n<p>The weekly layer needs no tools, no dismantling and no technician. It is five minutes at the opening, done by in-house staff after a short briefing. Our rule of thumb for the cadence is simple: if the opening matters when the alarm sounds, it gets walked once a week. A fire shutter inspection at this level is deliberately limited to what eyes can catch.<\/p>\n<ol>\n<li>Check the clearance. Pallets, stillages and parked vehicles stay out of the shutter&#8217;s travel zone on both sides.<\/li>\n<li>Look over the curtain and guides for bent slats, tears, holes, impact marks and signs the curtain has struck something.<\/li>\n<li>Check the release chain. Fusible links and cables must carry no paint, dust or grease, and nothing may be kinked or pinched.<\/li>\n<li>Confirm nothing foreign is fixed to the door assembly: no ducting, conduit, lighting or signage screwed to the curtain or hood.<\/li>\n<li>Report anything unusual. A new noise, a rubbing guide or a slow response goes on a work order the same day.<\/li>\n<\/ol>\n<p>Whoever walks the route needs two minutes of instruction and a card to carry. Show the crew the travel zone, the fusible link, the release arm and the label, so the five minutes are spent comparing the door against a picture rather than guessing. Facilities that rotate the duty across shift leads get a bonus: four pairs of eyes a month, each one comparing the door against its own last look.<\/p>\n<p>The clearance check is not housekeeping pedantry. OSHA&#8217;s exit route rules require routes to stay free and unobstructed, with no materials or equipment placed within them. The same rules put <a href=\"https:\/\/www.ecfr.gov\/current\/title-29\/subtitle-B\/chapter-XVII\/part-1910\/subpart-E\/section-1910.37\" target=\"_blank\" rel=\"noopener\">fire doors among the safeguards that must work at all times<\/a>. A curtain that cannot reach the floor because a rack was wheeled in front of it has failed before the fire arrives.<\/p>\n<p>Two quiet details finish the walk. The listing label on the bottom bar should stay legible and unobscured, and none of the visible parts should be missing or broken. Both points sit among the verification items inspectors check on rolling fire doors, and both are visible to any trained eye in seconds.<\/p>\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-weekly-r2.webp\" class=\"wp-image-5278\" alt=\"Three closed roll-up doors on a beige industrial building with a clear concrete apron in front\" width=\"1200\" height=\"675\" loading=\"lazy\" srcset=\"https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-weekly-r2.webp 1200w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-weekly-r2-300x169.webp 300w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-weekly-r2-1024x576.webp 1024w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-weekly-r2-768x432.webp 768w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-weekly-r2-18x10.webp 18w\" sizes=\"auto, (max-width: 1200px) 100vw, 1200px\" \/><\/figure>\n<h2 id=\"the-monthly-test-exercising-the-release\">The Monthly Test: Exercising the Release<\/h2>\n<p>The monthly layer adds motion. Where the weekly walk looks, the monthly test operates. It exercises the release chain under controlled conditions, so a seized trigger or a sticky linkage shows up in a drill rather than in an emergency. Some manufacturers build this in explicitly; one maker&#8217;s installation instructions call for the door&#8217;s safety features to be tested at least once a month.<\/p>\n<p>The shape of the test stays modest. Bar the opening so nobody and nothing can enter. Trip the test release from the local test switch or the alarm panel&#8217;s test signal. Watch the curtain descend under control, then reset it to standby. The preparation logic the drop-test guidance applies to annual testing holds here too: correct whatever the weekly checks flagged first, and clear the doorway before anything moves.<\/p>\n<div class=\"callout callout-warning\" style=\"border-left:4px solid #c0392b;background:#fdf3f1;padding:14px 18px;margin:24px 0;border-radius:4px;\">\n<p style=\"margin:0;\">A release exercise is a real closure. Keep people, trucks and stock out of the opening on both sides for the whole cycle, because the curtain does not negotiate.<\/p>\n<\/div>\n<p>Monthly is also the right cadence for one specific suspicion: the drop arm that someone tied back. A release arm wedged, blocked or tied out of the way turns the fastest trigger into decoration. That kind of interference is exactly what a monthly eye catches. Give the whole hardware set the discipline of a <a href=\"https:\/\/www.raxdoors.com\/blog\/sectional-door-hardware-maintenance\/\">maintenance schedule for door hardware<\/a>. Every part runs on its own clock, and every finding lands on a record.<\/p>\n<p>One boundary keeps the monthly layer honest. A monthly exercise is not a drop test, and it does not certify anything; the certification-grade procedure belongs to the trained technician who attends once a year. In-house teams verify behaviour, not compliance. Keeping that division clean protects the staff, who never stand under a free-falling curtain on purpose. It keeps the paperwork in the hands of the people qualified to sign it.<\/p>\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-monthly.webp\" class=\"wp-image-5267\" alt=\"Two closed roller shutters standing by on a light industrial wall\" width=\"1200\" height=\"800\" loading=\"lazy\" srcset=\"https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-monthly.webp 1200w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-monthly-300x200.webp 300w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-monthly-1024x683.webp 1024w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-monthly-768x512.webp 768w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-monthly-18x12.webp 18w\" sizes=\"auto, (max-width: 1200px) 100vw, 1200px\" \/><\/figure>\n<h2 id=\"the-annual-drop-test-what-the-standard-requires\">The Annual Drop Test: What the Standard Requires<\/h2>\n<p>Among industrial doors, this is the one judged by a single commanded descent each year. Once a year, the routine hands the door to a trained technician, because the annual event is a full test of the assembly&#8217;s automatic closing, not a visual pass. Under NFPA 80 as summarised in the <a href=\"https:\/\/www.dasma.com\/wp-content\/uploads\/pubs\/TechDataSheets\/RollingDoor\/TDS271.pdf\" target=\"_blank\" rel=\"noopener\">DASMA technical data sheet for rolling steel fire doors<\/a>, the procedure runs in four steps, in order.<\/p>\n<ol>\n<li>Pre-test visual inspection: the weekly checklist, run formally, with deficiencies corrected before anything moves.<\/li>\n<li>Operational test: open and close the door normally, watching for abnormal movement or damaged parts.<\/li>\n<li>Drop test one: fully open, then release, and confirm the door closes completely and rests on the sill or floor.<\/li>\n<li>Drop test two: reset the door, release it again, and confirm the automatic closing device reset correctly.<\/li>\n<\/ol>\n<p>Before any of the four steps, the guidance asks the technician to block access around both sides of the door with caution tape. Flammable substances near the opening are relocated. The ritual looks ceremonial from a distance. It exists because a drop test is the only moment when the curtain is commanded to fall on schedule. The area beneath it should hold nothing but floor.<\/p>\n<p>The descent itself is judged, not just the landing. NFPA 80 sets the average closing speed between 6 and 24 inches per second, which the same figures express as 152 to 610 millimetres per second. Faster reads as free fall, which is a serious fault in its own right. Slower reads as a curtain that may stall short of the floor. Each automatic closing option on the door gets exercised, and every detector and release device in the chain must prove it works.<\/p>\n<p>The second drop is the step facilities most often skip in a fire shutter inspection, and at their peril. A door that drops well but fails to reset has left the opening protected exactly once, which is no protection at all. The reset check, followed by a final visual pass for anything the test itself may have damaged, is what turns a successful drop into a documented state of readiness.<\/p>\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-annual-r2.webp\" class=\"wp-image-5279\" alt=\"Technician in blue overalls working at an industrial door with a manual chain hoist and a fire alarm callpoint\" width=\"1200\" height=\"800\" loading=\"lazy\" srcset=\"https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-annual-r2.webp 1200w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-annual-r2-300x200.webp 300w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-annual-r2-1024x683.webp 1024w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-annual-r2-768x512.webp 768w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-annual-r2-18x12.webp 18w\" sizes=\"auto, (max-width: 1200px) 100vw, 1200px\" \/><\/figure>\n<h2 id=\"obstructions-guides-and-the-opening-itself\">Obstructions, Guides and the Opening Itself<\/h2>\n<p>On most industrial doors the wear shows up in motion; on this one it hides in stillness. The opening is a component too, and it deserves the same line in the checklist as the curtain. Combustible storage creeps toward firewall openings in every busy building. The DASMA guidance suggests relocating flammable substances away from the opening, and the weekly route should read the floor as closely as the door. Most component findings are visible without dismantling.<\/p>\n<table style=\"width:100%;border-collapse:collapse;font-size:.92em;\">\n<tr style=\"background:#f2f2f2;\">\n<th style=\"border:1px solid #ccc;padding:6px;\">Component<\/th>\n<th style=\"border:1px solid #ccc;padding:6px;\">What to look for<\/th>\n<th style=\"border:1px solid #ccc;padding:6px;\">Verdict<\/th>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #ccc;padding:6px;\">Curtain slats<\/td>\n<td style=\"border:1px solid #ccc;padding:6px;\">Bent, torn or holed laths; metal fatigue at fixings<\/td>\n<td style=\"border:1px solid #ccc;padding:6px;\">Replace affected slats from the original maker<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #ccc;padding:6px;\">Endlocks<\/td>\n<td style=\"border:1px solid #ccc;padding:6px;\">Missing, broken, bent or loose<\/td>\n<td style=\"border:1px solid #ccc;padding:6px;\">Replace before the next operation<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #ccc;padding:6px;\">Bottom bar<\/td>\n<td style=\"border:1px solid #ccc;padding:6px;\">Bent angles, loose bolts, missing or painted-over label<\/td>\n<td style=\"border:1px solid #ccc;padding:6px;\">Repair and restore the label evidence<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #ccc;padding:6px;\">Guide assemblies<\/td>\n<td style=\"border:1px solid #ccc;padding:6px;\">Bent angles or channels, loose bolts, curtain entry misalignment<\/td>\n<td style=\"border:1px solid #ccc;padding:6px;\">Realign or replace; keep the fire expansion clearance intact<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #ccc;padding:6px;\">Hood and fascia<\/td>\n<td style=\"border:1px solid #ccc;padding:6px;\">Dents, holes, curtain rubbing, loose fasteners, missing supports<\/td>\n<td style=\"border:1px solid #ccc;padding:6px;\">Repair; confirm the flame baffle is intact where fitted<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #ccc;padding:6px;\">Drop and release arms<\/td>\n<td style=\"border:1px solid #ccc;padding:6px;\">Tied, blocked or wedged out of position<\/td>\n<td style=\"border:1px solid #ccc;padding:6px;\">Free immediately and re-test the release<\/td>\n<\/tr>\n<\/table>\n<p>Mounting and assembly bolts complete the round, checked tight and uncorroded against the maker&#8217;s installation instructions. Fire shutters belong to a wider family of <a href=\"https:\/\/www.raxdoors.com\/specialty-doors\/\">specialty doors<\/a> built for hazards a standard leaf cannot answer. Like any engineered product, they stay honest only when their fittings stay tight and their clearances stay clear.<\/p>\n<h2 id=\"when-a-drop-test-fails\">When a Drop Test Fails<\/h2>\n<p>A failed test converts the opening from an assumed protection into a known defect. The handling sequence matters as much as the finding. Report it to the responsible person, and record the failure with the immediate control measure. Then restrict access to the opening, arrange temporary fire separation where the compartment demands it, and repair and re-test. What never happens is business as usual under a shutter that will not close.<\/p>\n<p>Failures cluster into a short list, and most of them are cheap to fix when caught early.<\/p>\n<ul>\n<li>Damaged or misaligned guides that pinch the curtain mid-travel.<\/li>\n<li>Motor or brake faults that leave the descent uncontrolled or unpowered.<\/li>\n<li>Broken or painted-over fusible links that never release.<\/li>\n<li>Alarm interfaces disconnected by recent works, so the signal never arrives.<\/li>\n<li>Weak backup batteries that stall the closure in a power cut.<\/li>\n<li>Debris beneath the curtain that stops it short of the floor.<\/li>\n<\/ul>\n<p>The repair rule comes straight from the guidance: failed components are replaced with parts from the original manufacturer. DASMA is candid that components can fail during the drop test itself, and that the repair cost may sit outside the test fee. That is worth knowing before the appointment rather than after. Parts availability is the quiet variable for industrial doors of any age. Our component catalogue runs to twenty-one part families for precisely this reason, and a door whose spares are still catalogued returns to service in days, not weeks.<\/p>\n<div class=\"callout callout-danger\" style=\"border-left:4px solid #8e2020;background:#fbf0f0;padding:14px 18px;margin:24px 0;border-radius:4px;\">\n<p style=\"margin:0;\">A shutter that failed its drop test stays out of service until it is repaired and re-tested. An opening that cannot close in a fire is an unprotected opening, whatever the label on the curtain says.<\/p>\n<\/div>\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-failed.webp\" class=\"wp-image-5269\" alt=\"Weathered roller shutter with corrosion and peeling paint on an aging industrial wall\" width=\"1200\" height=\"800\" loading=\"lazy\" srcset=\"https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-failed.webp 1200w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-failed-300x200.webp 300w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-failed-1024x683.webp 1024w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-failed-768x512.webp 768w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/09\/stock-fire-shutter-weekly-inspection-guide-failed-18x12.webp 18w\" sizes=\"auto, (max-width: 1200px) 100vw, 1200px\" \/><\/figure>\n<h2 id=\"records-that-survive-the-audit\">Records That Survive the Audit<\/h2>\n<p>Every fire shutter inspection ends in paperwork, because the whole exercise exists to demonstrate proper operation, full closure and proper reset. DASMA publishes a standard drop test form for exactly this, recording the visual, operational and drop test stages as pass or fail with the door identified. Whether the form is DASMA&#8217;s, the service contractor&#8217;s or your own, the fields that matter are the same.<\/p>\n<ol>\n<li>Door identity and location, so the record cannot migrate between openings.<\/li>\n<li>Date and tester, with the technician&#8217;s qualification noted for the annual test.<\/li>\n<li>Results for the visual, operational and both drop stages, each a clear pass or fail.<\/li>\n<li>Defects found, corrective action taken and the parts used.<\/li>\n<li>Retest date after any failure, and the next test due.<\/li>\n<\/ol>\n<p>How long to keep the file has no single answer in print. Our rule is to keep the latest report permanently on file, keep the running log behind it, and follow whatever period the authority having jurisdiction or the insurer sets. What the record buys is defensible history. When an auditor, an insurer or a fire officer asks when the shutter last proved itself, the answer is a date and a signature, not a shrug.<\/p>\n<p>Pair the test record with the label evidence and the file is complete. The label carries the rating, and the report carries the state. Both together answer the question the way <a href=\"https:\/\/www.raxdoors.com\/blog\/hotel-fire-door-rating-guide\/\">fire door ratings are read in hotel buildings<\/a>. Certification shows what the assembly was built to do, and the test record shows that it still does it.<\/p>\n<p>Which is where the shutter from the opening scene comes back. The one that stopped short was not betrayed by its rating; it was betrayed by a year of nobody looking. The weekly walk, the monthly exercise and the annual drop test are unglamorous. They are also the difference between a compartment line that exists on a drawing and one that exists in a fire.<\/p>\n<p>The cadence sets the schedule; <a href=\"https:\/\/www.raxdoors.com\/blog\/fire-door-drop-test-procedure\/\">the fire door drop test procedure itself<\/a> is its own discipline &#8211; preparation, the judged descent, the reset drop and the records that keep the label valid.<\/p>\n<blockquote style=\"border-left:4px solid #c7a868;margin:24px 0;padding:10px 18px;background:#faf7f0;font-style:italic;\">\n<p style=\"margin:0;\">A fire shutter inspection is ten minutes borrowed from an ordinary week, spent so that the worst minute of the year finds a curtain that falls, seats and resets.<\/p>\n<p>The fire track runs beside the rest of the fleet, not inside it; <a href=\"https:\/\/www.raxdoors.com\/blog\/warehouse-door-maintenance-schedule\/\">the warehouse-wide door maintenance plan<\/a> shows where the weekly and annual compliance rows sit among the everyday doors.<\/p>\n<\/blockquote>\n<p>Inspection keeps a rated assembly compliant, but the material behind the rating decides how much abuse it survives between checks. Our overview of <a href=\"https:\/\/www.raxdoors.com\/blog\/high-performance-steel-doors\/\" target=\"_blank\" rel=\"noopener\">high performance steel doors<\/a> covers why steel hosts fire capability so well.<\/p>\n<h2 id=\"frequently-asked-questions\">Frequently Asked Questions<\/h2>\n<div class=\"faq-card\" style=\"border:1px solid #e3e3e3;border-radius:8px;padding:18px 20px;margin:14px 0;\">\n<h3 style=\"font-weight:700;margin:0 0 6px;\">How often does a fire shutter need to be inspected?<\/h3>\n<p style=\"margin:0;\">NFPA 80 sets the floor: inspection and a drop test at least annually by a trained technician. Weekly visual walks and monthly release exercises sit on top of that, following the manufacturer&#8217;s instructions.<\/p>\n<\/div>\n<div class=\"faq-card\" style=\"border:1px solid #e3e3e3;border-radius:8px;padding:18px 20px;margin:14px 0;\">\n<h3 style=\"font-weight:700;margin:0 0 6px;\">What is a fire shutter drop test?<\/h3>\n<p style=\"margin:0;\">The release is triggered with the door fully open. The curtain must descend under control and close fully onto the sill, then reset so a second drop proves the automatic closing works again.<\/p>\n<\/div>\n<div class=\"faq-card\" style=\"border:1px solid #e3e3e3;border-radius:8px;padding:18px 20px;margin:14px 0;\">\n<h3 style=\"font-weight:700;margin:0 0 6px;\">Can our own staff do the weekly checks?<\/h3>\n<p style=\"margin:0;\">Yes. The weekly routine is visual and clearance only: obstructions, curtain condition, release chain cleanliness and fault reporting. The annual drop test stays with a trained fire door technician.<\/p>\n<\/div>\n<div class=\"faq-card\" style=\"border:1px solid #e3e3e3;border-radius:8px;padding:18px 20px;margin:14px 0;\">\n<h3 style=\"font-weight:700;margin:0 0 6px;\">How fast should a fire shutter close?<\/h3>\n<p style=\"margin:0;\">The average closing speed must fall between 6 and 24 inches per second. Faster suggests free fall, slower risks stalling short of the floor, and either finding means the door fails the test.<\/p>\n<\/div>\n<div class=\"faq-card\" style=\"border:1px solid #e3e3e3;border-radius:8px;padding:18px 20px;margin:14px 0;\">\n<h3 style=\"font-weight:700;margin:0 0 6px;\">What happens if the shutter fails the drop test?<\/h3>\n<p style=\"margin:0;\">It stays out of service. Report and record the failure, apply an immediate control such as restricting the opening, repair with parts from the original manufacturer, then pass a repeat test.<\/p>\n<\/div>\n<p><script type=\"application\/ld+json\">\n{\n  \"@context\": \"https:\/\/schema.org\",\n  \"@type\": \"Article\",\n  \"headline\": \"Fire Shutter Inspection: A Weekly to Annual Plan\",\n  \"description\": \"A fire shutter inspection plan for facilities: a weekly walkthrough, a monthly release drill, the annual NFPA 80 drop test, failure handling and records.\",\n  \"author\": {\"@type\": \"Organization\", \"name\": \"RAX Door Technology\"},\n  \"publisher\": {\"@type\": \"Organization\", \"name\": \"RAX Door Technology\"}\n}\n<\/script><br \/>\n<script type=\"application\/ld+json\">\n{\n  \"@context\": \"https:\/\/schema.org\",\n  \"@type\": \"FAQPage\",\n  \"mainEntity\": [\n    {\"@type\": \"Question\", \"name\": \"How often does a fire shutter need to be inspected?\", \"acceptedAnswer\": {\"@type\": \"Answer\", \"text\": \"NFPA 80 sets the floor: inspection and a drop test at least annually by a trained technician. Weekly visual walks and monthly release exercises sit on top of that, following the manufacturer's instructions.\"}},\n    {\"@type\": \"Question\", \"name\": \"What is a fire shutter drop test?\", \"acceptedAnswer\": {\"@type\": \"Answer\", \"text\": \"The release is triggered with the door fully open. The curtain must descend under control and close fully onto the sill, then reset so a second drop proves the automatic closing works again.\"}},\n    {\"@type\": \"Question\", \"name\": \"Can our own staff do the weekly checks?\", \"acceptedAnswer\": {\"@type\": \"Answer\", \"text\": \"Yes. The weekly routine is visual and clearance only: obstructions, curtain condition, release chain cleanliness and fault reporting. The annual drop test stays with a trained fire door technician.\"}},\n    {\"@type\": \"Question\", \"name\": \"How fast should a fire shutter close?\", \"acceptedAnswer\": {\"@type\": \"Answer\", \"text\": \"The average closing speed must fall between 6 and 24 inches per second. Faster suggests free fall, slower risks stalling short of the floor, and either finding means the door fails the test.\"}},\n    {\"@type\": \"Question\", \"name\": \"What happens if the shutter fails the drop test?\", \"acceptedAnswer\": {\"@type\": \"Answer\", \"text\": \"It stays out of service. Report and record the failure, apply an immediate control such as restricting the opening, repair with parts from the original manufacturer, then pass a repeat test.\"}}\n  ]\n}\n<\/script><br \/>\n<script type=\"application\/ld+json\" id=\"evo301-geo-ai-block\">\n{\n  \"@context\": \"https:\/\/schema.org\",\n  \"@type\": \"ItemList\",\n  \"name\": \"GEO AI Optimization Block: Fire Shutter Inspection: A Weekly to Annual Plan\",\n  \"itemListElement\": [\n    {\n      \"@type\": \"Answer\",\n      \"name\": \"definition\",\n      \"text\": \"A fire shutter inspection is a three-cadence routine. Weekly, in-house staff walk the opening for clearances, curtain and guide condition, release-chain cleanliness and foreign attachments, and report faults. Monthly, the opening is barred and the release is exercised under control so a seized trigger or a tied-back drop arm shows up in a drill. Annually, a trained rolling steel fire door technician runs the formal procedure: pre-test visual inspection, operational test, a first drop to prove full closure on the sill within an average closing speed of 6 to 24 inches per second, and a second drop to prove the automatic closing device reset. Failures are recorded with an immediate control measure, repaired with parts from the original manufacturer, and confirmed by a repeat test, with the visual, operational and drop results kept on a pass\/fail record.\"\n    },\n    {\n      \"@type\": \"ListItem\",\n      \"position\": 1,\n      \"name\": \"data_statements\",\n      \"text\": \"Verified figures with sources: the annual inspection and drop test requirement by a trained rolling steel fire door systems technician, applying even to doors never operated, the four-step drop test procedure, the 6 to 24 inches per second average closing speed band from NFPA 80, the component checklist covering slats, endlocks, bottom bar, guide assemblies with fire expansion clearance, hood and flame baffle, and drop or release arms that must not be tied, blocked or wedged, the requirement to replace failed components with parts from the original manufacturer, and the DASMA drop test form recording visual, operational and drop results as pass or fail, all from the DASMA technical data sheet 271 (dasma.com); the exit route requirement that no materials or equipment may be placed within it and that fire doors must be in proper working order at all times from 29 CFR 1910.37 (ecfr.gov); release triggers including alarm interfaces, smoke detectors, fusible links and local test switches, the certificate-versus-installed-state distinction, the no-single-interval statement with routine checks, functional tests and professional servicing as separate layers, the common failure list and the failed-shutter control measures from a UK fire shutter drop test guide (ukdoorsandshutters.uk, single source); the monthly safety-feature test from one manufacturer's installation instructions (cooksondoor.com, single source); twenty-one OEM component part families, EN 13241 and EN 12453 compliance and EI60\/EI120 fire capability validated per project under EN 1634-1 from RAX Door Technology first-party specifications (raxdoors.com).\"\n    },\n    {\n      \"@type\": \"ListItem\",\n      \"position\": 2,\n      \"name\": \"entity_relations\",\n      \"text\": \"The inspection routine relates to the release chain (fire alarm interface, smoke detectors, fusible links, local test switch, drop and release arms), to the closure hardware (curtain slats, endlocks, bottom bar with listing label, guide assemblies with fire expansion clearance, hood and flame baffle), to the code frame (NFPA 80 annual inspection and drop test, OSHA 29 CFR 1910.36 and 1910.37 exit route and working-order rules, DASMA technical data sheets), to the records system (pass\/fail form, defect log, retest date, next due date), and to the product family (fire-rated roller shutters, specialty doors, OEM door components for spare parts supply).\"\n    },\n    {\n      \"@type\": \"ListItem\",\n      \"position\": 3,\n      \"name\": \"decision_rule\",\n      \"text\": \"Assign work by cadence and competence: weekly visual and clearance checks go to trained in-house staff; monthly controlled release exercises go to the maintenance team with the opening barred on both sides; the annual four-step drop test goes to a trained rolling steel fire door technician. Any deficiency found at a lower cadence is corrected before the next higher one runs. A failed drop test takes the shutter out of service immediately: record the failure, restrict or separate the opening, repair with original-manufacturer parts, and return it to service only after a passed repeat test with both drops and the reset verified.\"\n    }\n  ]\n}\n<\/script><\/p>\n","protected":false},"excerpt":{"rendered":"<p>Der j\u00e4hrliche Brandtest erreicht beim Shutting als letztes die Reihe. Ein Techniker dr\u00fcckt den Ausl\u00f6ser, und alle im Gang beobachten, wie ein Vorhang, der ein Jahr lang nicht bewegt wurde, \u00fcber die \u00d6ffnung herabsinkt. An einem guten Tag landet er auf der Schwelle und der Besuch geht weiter. An einem schlechten Tag bleibt er \u2026 <a title=\"Inspektion von Feuerschutzroll\u00e4den: Ein w\u00f6chentlicher bis j\u00e4hrlicher Plan\" class=\"read-more\" href=\"https:\/\/www.raxdoors.com\/de\/blog\/fire-shutter-weekly-inspection-guide\/\" aria-label=\"Mehr Informationen \u00fcber Feuerschutzroll\u00e4den-Inspektion: Ein w\u00f6chentlicher bis j\u00e4hrlicher Plan\">Weiterlesen<\/a><\/p>","protected":false},"author":1,"featured_media":5277,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":"","rank_math_title":"Fire Shutter Inspection: A Practical Weekly Checklist","rank_math_description":"A fire shutter inspection plan for facilities: a weekly walkthrough, a monthly release drill, the annual NFPA 80 drop test, failure handling and records.","rank_math_focus_keyword":"fire shutter inspection","rank_math_robots":"","rank_math_canonical_url":"","rank_math_facebook_title":"","rank_math_facebook_description":"","rank_math_twitter_title":"","rank_math_twitter_description":"","_yoast_wpseo_title":"","_yoast_wpseo_metadesc":"","_yoast_wpseo_focuskw":"","_yoast_wpseo_canonical":"","_yoast_wpseo_meta-robots-noindex":"","_yoast_wpseo_meta-robots-nofollow":"","_yoast_wpseo_opengraph-title":"","_yoast_wpseo_opengraph-description":"","_yoast_wpseo_twitter-title":"","_yoast_wpseo_twitter-description":"","_aioseo_title":"","_aioseo_description":"","_aioseo_keywords":"","_aioseo_robots_default":"","_aioseo_robots_noindex":"","_aioseo_og_title":"","_aioseo_og_description":"","_aioseo_twitter_title":"","_aioseo_twitter_description":"","aiosp_title":"","aiosp_description":"","aiosp_keywords":"","_seopress_titles_title":"","_seopress_titles_desc":"","_seopress_analysis_target_kw":"","_seopress_robots_canonical":"","_seopress_robots_index":"","_seopress_robots_follow":"","_seopress_social_fb_title":"","_seopress_social_fb_desc":"","_seopress_social_twitter_title":"","_seopress_social_twitter_desc":"","_genesis_title":"","_genesis_description":"","_genesis_canonical":"","_genesis_noindex":"","_genesis_nofollow":"","slim_seo":""},"categories":[10],"tags":[],"class_list":["post-5270","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-specialty-doors"],"_links":{"self":[{"href":"https:\/\/www.raxdoors.com\/de\/wp-json\/wp\/v2\/posts\/5270","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.raxdoors.com\/de\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.raxdoors.com\/de\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.raxdoors.com\/de\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/www.raxdoors.com\/de\/wp-json\/wp\/v2\/comments?post=5270"}],"version-history":[{"count":4,"href":"https:\/\/www.raxdoors.com\/de\/wp-json\/wp\/v2\/posts\/5270\/revisions"}],"predecessor-version":[{"id":6401,"href":"https:\/\/www.raxdoors.com\/de\/wp-json\/wp\/v2\/posts\/5270\/revisions\/6401"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.raxdoors.com\/de\/wp-json\/wp\/v2\/media\/5277"}],"wp:attachment":[{"href":"https:\/\/www.raxdoors.com\/de\/wp-json\/wp\/v2\/media?parent=5270"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.raxdoors.com\/de\/wp-json\/wp\/v2\/categories?post=5270"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.raxdoors.com\/de\/wp-json\/wp\/v2\/tags?post=5270"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}