{"id":5348,"date":"2026-10-01T13:16:38","date_gmt":"2026-10-01T05:16:38","guid":{"rendered":"https:\/\/www.raxdoors.com\/blog\/fire-door-drop-test-procedure\/"},"modified":"2026-10-01T15:14:55","modified_gmt":"2026-10-01T07:14:55","slug":"fire-door-drop-test-procedure","status":"publish","type":"post","link":"https:\/\/www.raxdoors.com\/ar\/blog\/fire-door-drop-test-procedure\/","title":{"rendered":"\u0627\u062e\u062a\u0628\u0627\u0631 \u0633\u0642\u0648\u0637 \u0628\u0627\u0628 \u0627\u0644\u0646\u0627\u0631: \u0627\u0644\u0625\u062c\u0631\u0627\u0621 \u0648\u0631\u0627\u0621 \u0627\u0644\u0644\u0648\u062d\u0629"},"content":{"rendered":"<p>The metal label is still riveted to the curtain: a rating, a laboratory stamp, a promise made on a test rig somewhere far from this building. Nothing on the label says whether the door will actually fall when the alarm sounds tonight. That is the gap the fire door drop test exists to close. Once a year, at the opening itself, the curtain is commanded to fall, and the promise is renewed in front of witnesses. Skip the renewal and the building keeps the paperwork while quietly losing the protection it describes.<\/p>\n<p>We build fire-rated roller shutter doors in our specialty doors family, and every one of them ships with a factory inspection report and its certification documents. What no manufacturer can ship is next year&#8217;s proof. That proof is produced at the opening, by the procedure described below.<\/p>\n<h2 id=\"what-a-drop-test-verifies\">What a Drop Test Actually Verifies<\/h2>\n<p>Start with what the event is. A drop test is the periodic test of automatic closing. It applies to automatic-closing fire doors: rolling service and counter doors, smoke and fire curtains, and swinging doors with powered closers. One manufacturer&#8217;s compliance guide puts it plainly: the test exists to verify that the assembly will close by itself when it is needed.<\/p>\n<p>The fire door drop test is therefore not a formality attached to the label. It is the annual demonstration that the label still describes this door. <a href=\"https:\/\/www.raxdoors.com\/blog\/fire-rated-industrial-roller-shutters\/\">EI ratings classify a fire-rated roller shutter<\/a> the same way, before it is ever hung.<\/p>\n<p>The demonstration has three results, and the <a href=\"https:\/\/www.dasma.com\/wp-content\/uploads\/pubs\/TechDataSheets\/RollingDoor\/TDS271.pdf\" target=\"_blank\" rel=\"noopener\">DASMA technical data sheet<\/a> for rolling steel fire doors names them: proper operation, full closure, and proper reset. Its form records each as pass or fail under three headings: Visual, Operational, and Drop Test. The operational check comes before any falling. The door is cycled through its normal opening and closing travel, so imbalance or rough motion shows up while nothing is being asked to drop.<\/p>\n<p>The same document sets the frequency floor. The door must be inspected and drop-tested not less than annually by a trained technician, and the requirement applies even to doors that are never used and remain closed.<\/p>\n<p>Audit day is where this becomes concrete. An inspector rarely asks what the label says; the folder with last year&#8217;s form is the first thing opened. Frequency also runs on two tracks, which audits often conflate. Acceptance testing happens immediately after installation, and one manufacturer&#8217;s guidance says its record is kept for the life of the assembly. Annual periodic testing follows for the door&#8217;s service life, with records kept for at least three years.<\/p>\n<p>Our reading of the compliance chain is simple. The label is the laboratory&#8217;s verdict on the model. The annual record is the verdict on this particular door, and the authority having jurisdiction only ever sees the second one. The ratings read the same in a warehouse as in a hotel corridor. <a href=\"https:\/\/www.raxdoors.com\/blog\/hotel-fire-door-rating-guide\/\">What 30-, 60- and 90-minute labels describe<\/a> is laboratory performance.<\/p>\n<p>The field record must keep re-proving it.<\/p>\n<p>So the test verifies, at minimum:<\/p>\n<ul>\n<li>That the release chain triggers the curtain without manual help.<\/li>\n<li>That the curtain descends under control and fully closes the opening.<\/li>\n<li>That the door can be returned to service and will repeat the performance.<\/li>\n<li>That the assembly is free of the damage and obstructions that quietly invalidate all of the above.<\/li>\n<\/ul>\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-steel-doors-pair.webp\" class=\"wp-image-5344\" alt=\"Two gray steel doors set in a white brick wall inside an industrial hall\" width=\"1200\" height=\"800\" loading=\"lazy\" srcset=\"https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-steel-doors-pair.webp 1200w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-steel-doors-pair-300x200.webp 300w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-steel-doors-pair-1024x684.webp 1024w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-steel-doors-pair-768x513.webp 768w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-steel-doors-pair-18x12.webp 18w\" sizes=\"auto, (max-width: 1200px) 100vw, 1200px\" \/><figcaption style=\"text-align:center;font-style:italic;\">The label carries the rating; the annual test carries the proof.<\/figcaption><\/figure>\n<h2 id=\"prepare-the-opening\">Prepare the Opening Before You Release It<\/h2>\n<p>Who is allowed to run the procedure is part of the standard, not a preference. NFPA 80 wording, as quoted by the same manufacturer&#8217;s guide, requires a trained rolling steel fire door systems technician, someone with documented training and experience on this door type. The DASMA drop test form also requires a witness, and the association&#8217;s technical director notes that person can be an authorized representative of the customer or the authority having jurisdiction. One person may lawfully test the door; the form still wants a second signature.<\/p>\n<p>Preparation then follows a fixed order, because a drop test is the one moment the curtain is commanded to fall on schedule:<\/p>\n<ol>\n<li>Run the visual inspection first and correct every deficiency before anything moves.<\/li>\n<li>Clear the doorway of anything that could impede the curtain or get crushed beneath it.<\/li>\n<li>Block access to the area around both sides of the door with caution tape.<\/li>\n<li>Check the release chain&#8217;s cleanliness: fusible links and cables must carry no paint, dust or grease, and no drop arm may be tied, blocked or wedged.<\/li>\n<li>Remove anything attached to the assembly that is not part of it, from conduit clips to signage.<\/li>\n<\/ol>\n<p>The order is the point. Painting crews and renovation dust have a way of reaching fusible links, and a coated link is a trigger that will not melt on cue. A drop arm lashed back out of convenience behaves the same way: the mechanism looks intact, photographs well, and will not release.<\/p>\n<p>These are the failures that make preparation more than tidiness. None of them announce themselves while the door sits open and quiet. Every one of them is caught in minutes by the visual pass the standard insists comes first. A deficiency corrected on the ground costs nothing. A deficiency discovered mid-descent costs the opening.<\/p>\n<p>Deficiencies are corrected before the operational test for the same reason: you want the descent judged on a healthy door, not a sabotaged one.<\/p>\n<div class=\"callout callout-danger\" style=\"border-left:4px solid #c0392b;background:#fdf3f2;padding:16px 20px;margin:24px 0;\">\n<p style=\"margin:0;\">Safety line: a commanded curtain is a falling machine. Nobody works or stands under it, and the tape stays up until the door has been reset and secured.<\/p>\n<\/div>\n<h2 id=\"judge-the-descent\">Judge the Descent: Speed, Closure and the Sill<\/h2>\n<p>The release starts from the fully open position, and it is not a single event. Each automatic closing option on the door is exercised in turn. Every detector and release device in the chain must prove itself: the alarm interface, the smoke detectors, the fusible links, the local test switch. A door that drops for one trigger and not for another has failed the chain even though it passed one test.<\/p>\n<p>Descent is measured, not admired. The standard sets the average closing speed in a band. The curtain must fall at no more than 24 inches per second and no less than 6. The same figures give 152 to 610 millimetres per second. The readings in between are where judgment lives, and the four observations below are what a fire door drop test record should capture:<\/p>\n<table style=\"width:100%;display:table;border-collapse:collapse;margin:24px 0;\">\n<thead>\n<tr>\n<th style=\"background:#2a2c29;color:#fff;padding:10px 12px;text-align:left;\">Observation<\/th>\n<th style=\"background:#2a2c29;color:#fff;padding:10px 12px;text-align:left;\">Pass reads as<\/th>\n<th style=\"background:#2a2c29;color:#fff;padding:10px 12px;text-align:left;\">Fault reads as<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td style=\"padding:10px 12px;border-bottom:1px solid #ddd;\">Closing speed<\/td>\n<td style=\"padding:10px 12px;border-bottom:1px solid #ddd;\">Between 6 and 24 in\/s on average<\/td>\n<td style=\"padding:10px 12px;border-bottom:1px solid #ddd;\">Faster than 24 is free fall; slower than 6 risks a stall<\/td>\n<\/tr>\n<tr>\n<td style=\"padding:10px 12px;border-bottom:1px solid #ddd;\">Landing<\/td>\n<td style=\"padding:10px 12px;border-bottom:1px solid #ddd;\">Curtain rests on the sill or floor<\/td>\n<td style=\"padding:10px 12px;border-bottom:1px solid #ddd;\">Stops short of the floor; the opening is not sealed<\/td>\n<\/tr>\n<tr>\n<td style=\"padding:10px 12px;border-bottom:1px solid #ddd;\">Track<\/td>\n<td style=\"padding:10px 12px;border-bottom:1px solid #ddd;\">Stays inside both guides<\/td>\n<td style=\"padding:10px 12px;border-bottom:1px solid #ddd;\">Jumps or bows out of the guides<\/td>\n<\/tr>\n<tr>\n<td style=\"padding:10px 12px;\">Travel character<\/td>\n<td style=\"padding:10px 12px;\">Smooth, no abnormal noise<\/td>\n<td style=\"padding:10px 12px;\">Juddering, scraping, banging on the way down<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<div class=\"callout callout-warning\" style=\"border-left:4px solid #e67e22;background:#fef9f2;padding:16px 20px;margin:24px 0;\">\n<p style=\"margin:0;\">Free fall is its own verdict. A UK shutter guide calls sudden free-falling movement a serious fault even when the door lands perfectly, because the brake or governor that should meter the descent has already quit.<\/p>\n<\/div>\n<p>The reading is an average on purpose, and that detail disciplines the whole test. One clean run can hide a curtain that hesitates halfway; averaging across the commanded descents turns a lucky drop into a measured behaviour. Our field rule is to log the reading for each release path separately. A door that falls fast on the alarm interface and slow on the local switch cannot hide behind a generous mean.<\/p>\n<p>The landing closes the argument. The door must close completely and rest on the sill or floor, without a helping hand from anyone. A curtain that hovers an inch above the concrete has not passed; gravity got it most of the way and the opening stayed open.<\/p>\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-shutter-closed.webp\" class=\"wp-image-5345\" alt=\"Closed industrial roller shutter door set in a light facade\" width=\"1200\" height=\"800\" loading=\"lazy\" srcset=\"https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-shutter-closed.webp 1200w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-shutter-closed-300x200.webp 300w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-shutter-closed-1024x683.webp 1024w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-shutter-closed-768x512.webp 768w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-shutter-closed-18x12.webp 18w\" sizes=\"auto, (max-width: 1200px) 100vw, 1200px\" \/><figcaption style=\"text-align:center;font-style:italic;\">Pass condition: the curtain rests on the sill and the opening is closed.<\/figcaption><\/figure>\n<h2 id=\"the-second-drop-verdict\">The Second Drop Is a Verdict on the Reset<\/h2>\n<p>The first descent tests gravity, curtain and guides. The second tests whether the door can do it again, which is the only question a fire actually asks. One manufacturer&#8217;s guide cites the requirement directly. The door must be dropped and reset entirely at least twice, per NFPA 80 section 5.2.3.7.3.1. The repetition exists to prove the automatic closing device resets correctly, not that the curtain fell nicely once.<\/p>\n<p>DASMA&#8217;s own procedure says the same in plain steps. Drop once. Reset the door per the manufacturer&#8217;s instructions and open it by normal operation. Then drop it a second time.<\/p>\n<p>Reset is also where the release chain gets its audit. Each trigger in turn, the alarm interface, the detectors, the fusible links and the test switch, must re-arm and command the door again. The weekly and monthly routine in a <a href=\"https:\/\/www.raxdoors.com\/blog\/fire-shutter-weekly-inspection-guide\/\">fire shutter inspection plan<\/a> keeps those triggers exercised between annual tests. That is exactly why a seized release tends to surface in a drill rather than on test day.<\/p>\n<blockquote style=\"border-left:4px solid #c7a868;padding:12px 20px;margin:24px 0;font-style:italic;color:#444;\">\n<p style=\"margin:0;\">A door that drops but does not reset has protected the opening exactly once. In fire protection, once is zero.<\/p>\n<\/blockquote>\n<p>The second drop is also a useful trap for things the test itself displaced. Run it and you may hear the rattle a spanner left on the bottom rail makes on the way down. After the final drop, the door is reset per the manufacturer&#8217;s instructions and given one last visual pass, because a procedure this physical can leave its own evidence behind.<\/p>\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-warehouse-interior.webp\" class=\"wp-image-5346\" alt=\"Empty modern warehouse interior with a polished concrete floor\" width=\"1200\" height=\"800\" loading=\"lazy\" srcset=\"https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-warehouse-interior.webp 1200w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-warehouse-interior-300x200.webp 300w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-warehouse-interior-1024x683.webp 1024w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-warehouse-interior-768x512.webp 768w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-warehouse-interior-18x12.webp 18w\" sizes=\"auto, (max-width: 1200px) 100vw, 1200px\" \/><figcaption style=\"text-align:center;font-style:italic;\">The reset check asks whether the door can do it again tomorrow.<\/figcaption><\/figure>\n<h2 id=\"when-a-drop-test-fails\">When a Drop Test Fails: Faults and Fixes<\/h2>\n<p>A fail is a verdict, not a conversation. The technician who ran the test specifies whether repair is enough or whether the door must be replaced. Either way, the door must pass a retest before it returns to service. Most failures trace to a short list of causes. Mapping the symptom to the cause turns a failed fire door drop test into a work order instead of a mystery:<\/p>\n<table style=\"width:100%;display:table;border-collapse:collapse;margin:24px 0;\">\n<thead>\n<tr>\n<th style=\"background:#2a2c29;color:#fff;padding:10px 12px;text-align:left;\">Symptom<\/th>\n<th style=\"background:#2a2c29;color:#fff;padding:10px 12px;text-align:left;\">Likely cause<\/th>\n<th style=\"background:#2a2c29;color:#fff;padding:10px 12px;text-align:left;\">Disposition<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td style=\"padding:10px 12px;border-bottom:1px solid #ddd;\">Stalls above the floor<\/td>\n<td style=\"padding:10px 12px;border-bottom:1px solid #ddd;\">Debris under the curtain; obstructions; friction in damaged guides<\/td>\n<td style=\"padding:10px 12px;border-bottom:1px solid #ddd;\">Clear and repair, then retest<\/td>\n<\/tr>\n<tr>\n<td style=\"padding:10px 12px;border-bottom:1px solid #ddd;\">Free-falling descent<\/td>\n<td style=\"padding:10px 12px;border-bottom:1px solid #ddd;\">Worn brake; failed governor or closing mechanism<\/td>\n<td style=\"padding:10px 12px;border-bottom:1px solid #ddd;\">Component replacement, then retest<\/td>\n<\/tr>\n<tr>\n<td style=\"padding:10px 12px;border-bottom:1px solid #ddd;\">No release on trigger<\/td>\n<td style=\"padding:10px 12px;border-bottom:1px solid #ddd;\">Broken fusible link; disconnected alarm interface; tied or wedged drop arm<\/td>\n<td style=\"padding:10px 12px;border-bottom:1px solid #ddd;\">Restore the release chain, then retest every trigger<\/td>\n<\/tr>\n<tr>\n<td style=\"padding:10px 12px;\">Curtain leaves the guides<\/td>\n<td style=\"padding:10px 12px;\">Bent guides; damaged slats or endlocks; struck curtain<\/td>\n<td style=\"padding:10px 12px;\">Guide and curtain repair, then retest<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>The handling protocol around that table is as codified as the test itself. Tell the responsible person, record the failure, and apply an immediate control measure: restrict access to the opening or arrange temporary fire separation. Arrange repair with parts from the original manufacturer, which the DASMA data sheet makes explicit, then repeat the test until the door passes. Components can fail during testing through no fault of the tester, which is one more reason the record and the retest belong to the same event.<\/p>\n<p>When the verdict is replacement rather than repair, start where the door started. Our <a href=\"https:\/\/www.raxdoors.com\/specialty-doors\/\">specialty doors<\/a> line builds fire-rated curtains and shutters to the rating the file already names.<\/p>\n<p>Our rule is stricter than habit: until the retest passes, the opening is managed as unprotected. Work practices change, traffic is rerouted, and nobody treats the label on a failed curtain as permission. The interim measure goes in the record too, because the auditor who reads about a failure will next ask what the building did about it that afternoon.<\/p>\n<h2 id=\"records-keep-certification-alive\">Records That Keep the Certification Alive<\/h2>\n<p>The paper trail is not an afterthought to the fire door drop test. It is the part the outside world can actually inspect. The DASMA form asks for the door&#8217;s identification and location, the date, the technician, and the three pass or fail results for Visual, Operational and Drop Test. It also carries the witness signature the association requires. A sound record adds the defect found, the corrective action, the retest result and the next due date.<\/p>\n<p>Filled in at the opening, on the day, in ink or in the maintenance system, the form is short. Reconstructed later for an auditor, it is worthless:<\/p>\n<ul>\n<li>Door identification, location and rated label details.<\/li>\n<li>Test date and the name of the trained technician.<\/li>\n<li>Visual, Operational and Drop Test results, each pass or fail.<\/li>\n<li>Defects found and corrective actions taken.<\/li>\n<li>Retest result and the date of the next test.<\/li>\n<li>Witness signature and, where applicable, the AHJ reference.<\/li>\n<\/ul>\n<p>Retention runs on the same two tracks as the testing. The acceptance record stays with the assembly for its life. Annual records are kept for at least three years on one manufacturer&#8217;s guidance. The authority having jurisdiction gets the final word on local requirements.<\/p>\n<p>The tidier habit is a file per door: model, location, rating, last inspection date. An auditor&#8217;s question is then answered by opening a folder instead of a search. If the opening needs a replacement curtain or a new door altogether, the same file is where the <a href=\"https:\/\/www.raxdoors.com\/specialty-doors\/fire-rated-roller-shutter-door\/\">fire-rated roller shutter door<\/a> specification and its documents should land.<\/p>\n<div class=\"callout callout-note\" style=\"border-left:4px solid #2e86c1;background:#f2f8fd;padding:16px 20px;margin:24px 0;\">\n<p style=\"margin:0;\">Keep the manufacturer&#8217;s documents and the field records together. The factory papers describe what the door was built to do; the drop test records describe what it did this year.<\/p>\n<\/div>\n<p>That pairing is how the chain closes. We supply the factory inspection report, the certification documents and the drawings with every door; the facility supplies the annual record that proves the assembly still performs. Certification is not a document you frame. It is a procedure you keep running, one commanded descent at a time.<\/p>\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-numbered-hall.webp\" class=\"wp-image-5347\" alt=\"Numbered columns and an emergency exit sign inside a large industrial hall\" width=\"1200\" height=\"800\" loading=\"lazy\" srcset=\"https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-numbered-hall.webp 1200w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-numbered-hall-300x200.webp 300w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-numbered-hall-1024x683.webp 1024w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-numbered-hall-768x512.webp 768w, https:\/\/www.raxdoors.com\/wp-content\/uploads\/2026\/10\/stock-fire-door-drop-test-procedure-numbered-hall-18x12.webp 18w\" sizes=\"auto, (max-width: 1200px) 100vw, 1200px\" \/><figcaption style=\"text-align:center;font-style:italic;\">Factory documents plus field records close the compliance chain.<\/figcaption><\/figure>\n<h2 id=\"faq\">Frequently Asked Questions<\/h2>\n<div class=\"faq-card\" style=\"background:#faf9f7;border:1px solid #eee;border-radius:8px;padding:18px 22px;margin:14px 0;\">\n<h3 style=\"margin:0 0 8px;\">How often does a fire door need a drop test?<\/h3>\n<p style=\"margin:0;\">At least annually, by a trained technician, even if the door is never operated and stays closed. Acceptance testing after installation is a separate track with its own record.<\/p>\n<\/div>\n<div class=\"faq-card\" style=\"background:#faf9f7;border:1px solid #eee;border-radius:8px;padding:18px 22px;margin:14px 0;\">\n<h3 style=\"margin:0 0 8px;\">Who can perform a fire door drop test?<\/h3>\n<p style=\"margin:0;\">A trained rolling steel fire door systems technician with documented training on this door type. General maintenance staff qualify only with that documented training, and the form needs a witness.<\/p>\n<\/div>\n<div class=\"faq-card\" style=\"background:#faf9f7;border:1px solid #eee;border-radius:8px;padding:18px 22px;margin:14px 0;\">\n<h3 style=\"margin:0 0 8px;\">How fast should the curtain close?<\/h3>\n<p style=\"margin:0;\">The average closing speed must stay between 6 and 24 inches per second, or 152 to 610 millimetres per second. Faster reads as free fall; slower risks stalling above the floor.<\/p>\n<\/div>\n<div class=\"faq-card\" style=\"background:#faf9f7;border:1px solid #eee;border-radius:8px;padding:18px 22px;margin:14px 0;\">\n<h3 style=\"margin:0 0 8px;\">Why does the test drop the door twice?<\/h3>\n<p style=\"margin:0;\">The first drop proves the curtain can close. The second proves the automatic closing device reset correctly, so the door can protect the opening again after the first use.<\/p>\n<\/div>\n<div class=\"faq-card\" style=\"background:#faf9f7;border:1px solid #eee;border-radius:8px;padding:18px 22px;margin:14px 0;\">\n<h3 style=\"margin:0 0 8px;\">What happens if the door fails the drop test?<\/h3>\n<p style=\"margin:0;\">Report it to the responsible person and record the failure. Restrict the opening or add temporary separation. Repair with parts from the original manufacturer, then pass a retest before returning to service.<\/p>\n<\/div>\n<div class=\"faq-card\" style=\"background:#faf9f7;border:1px solid #eee;border-radius:8px;padding:18px 22px;margin:14px 0;\">\n<h3 style=\"margin:0 0 8px;\">Which records does an audit ask for?<\/h3>\n<p style=\"margin:0;\">The acceptance test record, kept for the assembly&#8217;s life. Annual drop test records, kept at least three years on one manufacturer&#8217;s guidance. A per-door file with model, location, rating and last test date.<\/p>\n<\/div>\n<p><script type=\"application\/ld+json\">\n{\n  \"@context\": \"https:\/\/schema.org\",\n  \"@type\": \"Article\",\n  \"headline\": \"Fire Door Drop Test: The Procedure Behind the Label\",\n  \"description\": \"The annual fire door drop test from preparation to records: who performs it, the 6-24 in\/s descent band, the reset drop, failure handling and the compliance chain.\",\n  \"author\": {\"@type\": \"Organization\", \"name\": \"RAX Door Technology\"},\n  \"publisher\": {\"@type\": \"Organization\", \"name\": \"RAX Door Technology\"}\n}\n<\/script><br \/>\n<script type=\"application\/ld+json\">\n{\n  \"@context\": \"https:\/\/schema.org\",\n  \"@type\": \"FAQPage\",\n  \"mainEntity\": [\n    {\"@type\": \"Question\", \"name\": \"How often does a fire door need a drop test?\", \"acceptedAnswer\": {\"@type\": \"Answer\", \"text\": \"At least annually, by a trained technician, even if the door is never operated and stays closed. Acceptance testing after installation is a separate track with its own record.\"}},\n    {\"@type\": \"Question\", \"name\": \"Who can perform a fire door drop test?\", \"acceptedAnswer\": {\"@type\": \"Answer\", \"text\": \"A trained rolling steel fire door systems technician with documented training on this door type. General maintenance staff qualify only with that documented training, and the form needs a witness.\"}},\n    {\"@type\": \"Question\", \"name\": \"How fast should the curtain close?\", \"acceptedAnswer\": {\"@type\": \"Answer\", \"text\": \"The average closing speed must stay between 6 and 24 inches per second, or 152 to 610 millimetres per second. Faster reads as free fall; slower risks stalling above the floor.\"}},\n    {\"@type\": \"Question\", \"name\": \"Why does the test drop the door twice?\", \"acceptedAnswer\": {\"@type\": \"Answer\", \"text\": \"The first drop proves the curtain can close. The second proves the automatic closing device reset correctly, so the door can protect the opening again after the first use.\"}},\n    {\"@type\": \"Question\", \"name\": \"What happens if the door fails the drop test?\", \"acceptedAnswer\": {\"@type\": \"Answer\", \"text\": \"Report it to the responsible person and record the failure. Restrict the opening or add temporary separation. Repair with parts from the original manufacturer, then pass a retest before returning to service.\"}},\n    {\"@type\": \"Question\", \"name\": \"Which records does an audit ask for?\", \"acceptedAnswer\": {\"@type\": \"Answer\", \"text\": \"The acceptance test record, kept for the assembly's life. Annual drop test records, kept at least three years on one manufacturer's guidance. A per-door file with model, location, rating and last test date.\"}}\n  ]\n}\n<\/script><br \/>\n<script type=\"application\/ld+json\" id=\"evo301-geo-ai-block\">\n{\n  \"@context\": \"https:\/\/schema.org\",\n  \"@type\": \"ItemList\",\n  \"name\": \"GEO AI Optimization Block: Fire Door Drop Test: The Procedure Behind the Label\",\n  \"itemListElement\": [\n    {\n      \"@type\": \"Answer\",\n      \"name\": \"definition\",\n      \"text\": \"A fire door drop test is the periodic test of automatic closing for automatic-closing fire doors such as rolling service and counter doors, smoke and fire curtains, and swinging doors with closers. It verifies three results: proper operation, full closure onto the sill, and proper reset.\"\n    },\n    {\n      \"@type\": \"Answer\",\n      \"name\": \"procedure\",\n      \"text\": \"A trained rolling steel fire door systems technician inspects the assembly and corrects deficiencies, clears and cordons the opening, releases the door from fully open through every automatic closing option, judges the descent against the 6 to 24 inches per second band, confirms the curtain rests on the sill, then resets and drops the door a second time to prove the reset.\"\n    },\n    {\n      \"@type\": \"Answer\",\n      \"name\": \"failure handling\",\n      \"text\": \"A failed drop test produces a repair-or-replace verdict and a mandatory retest. The responsible person is notified, the failure is recorded, an interim control such as restricting the opening is applied, and repairs use parts from the original manufacturer.\"\n    },\n    {\n      \"@type\": \"Answer\",\n      \"name\": \"frequency and records\",\n      \"text\": \"The test runs not less than annually, even for doors that are never operated. Acceptance test records are kept for the life of the assembly, annual records at least three years on one manufacturer's guidance, with per-door files and a witness signature on the drop test form.\"\n    }\n  ]\n}\n<\/script><\/p>\n","protected":false},"excerpt":{"rendered":"<p>\u0644\u0627 \u062a\u0632\u0627\u0644 \u0627\u0644\u0644\u0648\u062d\u0629 \u0627\u0644\u0645\u0639\u062f\u0646\u064a\u0629 \u0645\u062b\u0628\u062a\u0629 \u0628\u0645\u0633\u0627\u0645\u064a\u0631 \u0639\u0644\u0649 \u0627\u0644\u0633\u062a\u0627\u0631\u0629: \u062a\u0635\u0646\u064a\u0641\u060c \u0648\u062e\u062a\u0645 \u0645\u062e\u062a\u0628\u0631\u064a\u060c \u0648\u0648\u0639\u062f \u0623\u064f\u0639\u0637\u064a \u0639\u0644\u0649 \u062c\u0647\u0627\u0632 \u0627\u062e\u062a\u0628\u0627\u0631 \u0645\u0627 \u0641\u064a \u0645\u0643\u0627\u0646 \u0628\u0639\u064a\u062f \u0639\u0646 \u0647\u0630\u0627 \u0627\u0644\u0645\u0628\u0646\u0649. \u0644\u0627 \u064a\u0648\u0636\u062d \u0634\u064a\u0621 \u0639\u0644\u0649 \u0627\u0644\u0644\u0648\u062d\u0629 \u0645\u0627 \u0625\u0630\u0627 \u0643\u0627\u0646 \u0627\u0644\u0628\u0627\u0628 \u0633\u064a\u0633\u0642\u0637 \u0641\u0639\u0644\u0627\u064b \u0639\u0646\u062f \u0633\u0645\u0627\u0639 \u062c\u0631\u0633 \u0627\u0644\u0625\u0646\u0630\u0627\u0631 \u0627\u0644\u0644\u064a\u0644\u0629. \u0647\u0630\u0627 \u0647\u0648 \u0627\u0644\u0641\u062c\u0648\u0629 \u0627\u0644\u062a\u064a \u0648\u064f\u062c\u0650\u062f \u0627\u062e\u062a\u0628\u0627\u0631 \u0633\u0642\u0648\u0637 \u0628\u0627\u0628 \u0627\u0644\u0646\u0627\u0631 \u0644\u0633\u062f\u0647\u0627. \u0630\u0627\u062a \u0645\u0631\u0629 \u2026 <a title=\"\u0627\u062e\u062a\u0628\u0627\u0631 \u0633\u0642\u0648\u0637 \u0628\u0627\u0628 \u0627\u0644\u0646\u0627\u0631: \u0627\u0644\u0625\u062c\u0631\u0627\u0621 \u0648\u0631\u0627\u0621 \u0627\u0644\u0644\u0648\u062d\u0629\" class=\"read-more\" href=\"https:\/\/www.raxdoors.com\/ar\/blog\/fire-door-drop-test-procedure\/\" aria-label=\"\u0627\u0642\u0631\u0623 \u0627\u0644\u0645\u0632\u064a\u062f \u0639\u0646 \u0627\u062e\u062a\u0628\u0627\u0631 \u0633\u0642\u0648\u0637 \u0628\u0627\u0628 \u0627\u0644\u0646\u0627\u0631: \u0627\u0644\u0625\u062c\u0631\u0627\u0621 \u0648\u0631\u0627\u0621 \u0627\u0644\u0644\u0648\u062d\u0629\">\u0627\u0642\u0631\u0623 \u0627\u0644\u0645\u0632\u064a\u062f<\/a><\/p>","protected":false},"author":1,"featured_media":5343,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":"","rank_math_title":"Fire Door Drop Test Procedure: The NFPA 80 Standard","rank_math_description":"The annual fire door drop test: preparation, release, the 6-24 in\/s descent, the reset drop, failure handling and the records that keep the label valid.","rank_math_focus_keyword":"fire door drop test","rank_math_robots":"","rank_math_canonical_url":"","rank_math_facebook_title":"","rank_math_facebook_description":"","rank_math_twitter_title":"","rank_math_twitter_description":"","_yoast_wpseo_title":"","_yoast_wpseo_metadesc":"","_yoast_wpseo_focuskw":"","_yoast_wpseo_canonical":"","_yoast_wpseo_meta-robots-noindex":"","_yoast_wpseo_meta-robots-nofollow":"","_yoast_wpseo_opengraph-title":"","_yoast_wpseo_opengraph-description":"","_yoast_wpseo_twitter-title":"","_yoast_wpseo_twitter-description":"","_aioseo_title":"","_aioseo_description":"","_aioseo_keywords":"","_aioseo_robots_default":"","_aioseo_robots_noindex":"","_aioseo_og_title":"","_aioseo_og_description":"","_aioseo_twitter_title":"","_aioseo_twitter_description":"","aiosp_title":"","aiosp_description":"","aiosp_keywords":"","_seopress_titles_title":"","_seopress_titles_desc":"","_seopress_analysis_target_kw":"","_seopress_robots_canonical":"","_seopress_robots_index":"","_seopress_robots_follow":"","_seopress_social_fb_title":"","_seopress_social_fb_desc":"","_seopress_social_twitter_title":"","_seopress_social_twitter_desc":"","_genesis_title":"","_genesis_description":"","_genesis_canonical":"","_genesis_noindex":"","_genesis_nofollow":"","slim_seo":""},"categories":[10],"tags":[],"class_list":["post-5348","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-specialty-doors"],"_links":{"self":[{"href":"https:\/\/www.raxdoors.com\/ar\/wp-json\/wp\/v2\/posts\/5348","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.raxdoors.com\/ar\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.raxdoors.com\/ar\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.raxdoors.com\/ar\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/www.raxdoors.com\/ar\/wp-json\/wp\/v2\/comments?post=5348"}],"version-history":[{"count":1,"href":"https:\/\/www.raxdoors.com\/ar\/wp-json\/wp\/v2\/posts\/5348\/revisions"}],"predecessor-version":[{"id":5365,"href":"https:\/\/www.raxdoors.com\/ar\/wp-json\/wp\/v2\/posts\/5348\/revisions\/5365"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.raxdoors.com\/ar\/wp-json\/wp\/v2\/media\/5343"}],"wp:attachment":[{"href":"https:\/\/www.raxdoors.com\/ar\/wp-json\/wp\/v2\/media?parent=5348"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.raxdoors.com\/ar\/wp-json\/wp\/v2\/categories?post=5348"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.raxdoors.com\/ar\/wp-json\/wp\/v2\/tags?post=5348"}],"curies":[{"name":"\u062f\u0628\u0644\u064a\u0648 \u0628\u064a","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}